2022-09-12 07:25:01 -0500 received badge  Popular Question (source)
2019-11-18 08:31:00 -0500 marked best answer How to deal with weather converter warnings: direct normal radiation=.....Wh/m²

When running the EP weather converter on custom weather input files, warnings as below occur:

Warning ** Direct Normal Radiation=  1114.8 Wh/m² on date= 3/21 at hour=12
Warning ** Global Horizontal Radiation=  1211.4 Wh/m² on date= 4/ 9 at hour=14

This warnings seem to occur especially, if there has been rapid temperature rise in past few hours with changes in cloud cover, Wh/m² estimates ranging between appr. 1100-1550 in my test examples.

What are reasons for such warnings and what should be done in response ?

2019-10-24 18:32:49 -0500 received badge  Necromancer (source)
2019-01-06 21:55:34 -0500 received badge  Popular Question (source)
2018-07-20 11:34:50 -0500 answered a question How to Clear Warnings after Running OS Model

The warnings about invalid ScheduleTypeLimits can be eliminated by replacing the quoted ScheduleTypeLimits. The warning

2018-07-20 11:20:05 -0500 commented answer How to set VAV mass flow rates by EMS?

Did you change the Zone Minimum Air Flow Input Method to Scheduled ?

2018-07-09 02:37:11 -0500 commented answer How to set VAV mass flow rates by EMS?

did it work for you ?

2018-07-06 02:13:30 -0500 answered a question How to set VAV mass flow rates by EMS?

Instead of directly manipulating mass flow rates, I would propose using Minimum Air Flow Fraction Schedule(s) for AirTer

2018-06-30 06:02:28 -0500 edited question Why do IT Equipment Air Inlet Temperatures deviate from Supply Air Node Temperatures ?

Why do IT Equipment Air Inlet Temperatures deviate from Supply Air Node Temperatures ? My EnergyPlus model contains IT E

2018-06-30 06:01:34 -0500 asked a question Why do IT Equipment Air Inlet Temperatures deviate from Supply Air Node Temperatures ?

Why do IT Equipment Air Inlet Temperatures deviate from Supply Air Node Temperatures ? My EnergyPlus model contains IT E

2018-06-26 05:33:16 -0500 commented question Why does Controller:OutdoorAir not set OA-Flow to zero as specified ?

OK, here is a temporary download link

2018-06-22 05:28:12 -0500 edited question OpenStudio crashing with IDF import (Versions 2.1, 2.5)

OpenStudio crashing with IDF import (Versions 2.1, 2.5) When trying to import the IDF example file 1ZoneDataCenterCRAC_w

2018-06-22 05:20:55 -0500 marked best answer DView with incorrect variable descriptors

When opening DView (instead of ResultsViewer) for viewing OpenStudio 2.5. / EnergyPlus 8.9 results, DView adds a superfluous "**Design Day**" to every variable name, as you can see below:

image description

In ResultsViewer, on the other hand, there is no such extension of variable names, which proves that DView display is wrong (including axes labels).

Can Software developers confirm this as a BUG ?

2018-06-21 08:51:10 -0500 marked best answer OS 2.5: PlantEquipmentOperationSchemes: missing property

I have simple water loop as follows:

image description

It contains the tank of an air-to-water heatpump water heater attached to a zone, and a hot water user.

When running the osm model, the simulation crashes with the following err messages:


Program Version,EnergyPlus, Version 8.9.0-eba93e8e1b, YMD=2018.06.20 10:13,
   ** Severe  ** <root>[PlantEquipmentOperationSchemes][HotWaterLoop Operation Schemes] - Missing required property 'control_scheme_1_name'.
   ** Severe  ** <root>[PlantEquipmentOperationSchemes][HotWaterLoop Operation Schemes] - Missing required property 'control_scheme_1_object_type'.
   ** Severe  ** <root>[PlantEquipmentOperationSchemes][HotWaterLoop Operation Schemes] - Missing required property 'control_scheme_1_schedule_name'.
   **  Fatal  ** Errors occurred on processing input file. Preceding condition(s) cause termination.
   ...Summary of Errors that led to program termination:
   ..... Reference severe error count=3
   ..... Last severe error=<root>[PlantEquipmentOperationSchemes][HotWaterLoop Operation Schemes] - Missing required property 'control_scheme_1_schedule_name'.
   ************* Warning:  Node connection errors not checked - most system input has not been read (see previous warning).
   ************* Fatal error -- final processing.  Program exited before simulations began.  See previous error messages.
   ************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
   ************* EnergyPlus Sizing Error Summary. During Sizing: 0 Warning; 0 Severe Errors.
   ************* EnergyPlus Terminated--Fatal Error Detected. 0 Warning; 3 Severe Errors; Elapsed Time=00hr 00min  0.17sec

Apparently, OpenStudio has generated an incomplete IDF file. Did I miss anything necessary to specify ?

2018-06-21 08:50:32 -0500 commented question DView with incorrect variable descriptors

I was using Windows10. Anyway, "Run for Sizing Periods" was meant in addition to running the simulation for the weather

2018-06-21 05:42:56 -0500 commented answer OS 2.5: PlantEquipmentOperationSchemes: missing property

comprehensive answer: THANKS !

2018-06-21 05:36:55 -0500 commented question DView with incorrect variable descriptors

here is a time-limited download link, but the reported phenomenon seems to be occurring with any idf model; have you no

2018-06-21 03:35:27 -0500 answered a question Why does Controller:OutdoorAir not set OA-Flow to zero as specified ?

A solution that works is as follows: Add a Maximum Outdoor Air Fraction Schedule to Controller:OutdoorAir which is EMS-

2018-06-21 02:21:34 -0500 commented question Why does Controller:OutdoorAir not set OA-Flow to zero as specified ?

the entries for the VAV object are: AirTerminal:SingleDuct:VAV:NoReheat Name = Main Zone VAV Air

2018-06-21 01:28:26 -0500 commented question OS 2.5: PlantEquipmentOperationSchemes: missing property

here is the time-limited download link:

2018-06-20 11:31:14 -0500 commented question OS 2.5: PlantEquipmentOperationSchemes: missing property

Bien Sur ! To which email address should I send it, or can I directly upload it to unmethours ? (relatively small file)

2018-06-20 11:28:02 -0500 commented answer How to utilize zone exhaust air for heatpump water heaters ?

This solution is OK if the HPWH has to deal with only one zone. In order to use it as an air cooling device, it is nece

2018-06-20 11:25:48 -0500 marked best answer How to utilize zone exhaust air for heatpump water heaters ?

Modeliing a premise with very high internal heat gains such as a data center, it looks reasonable to utilize the zone(s) warm exhaust air with air-to-water heat pumps for producing hot water and simultaneously cooling the air in the airloop. While IDF Editor allows inserting an air-to-water heatpump water heater into the airloop, EnergyPlus however identifies this as "invalid component" in the airloop.

Are there any good alternatives in OpenStudio or EnergyPlus to solve this problem ?

2018-06-20 06:08:56 -0500 asked a question OS 2.5: PlantEquipmentOperationSchemes: missing property

OS 2.5: PlantEquipmentOperationSchemes: missing property I have simple water loop as follows: It contains the tank of

2018-06-20 02:54:13 -0500 asked a question Why does Controller:OutdoorAir not set OA-Flow to zero as specified ?

Why does Controller:OutdoorAir not set OA-Flow to zero as specified ? I have a simple airloop as shown below: If Out

2018-06-20 02:43:16 -0500 edited question DView with incorrect variable descriptors

DView with incorrect variable descriptors When opening DView (instead of ResultsViewer) for viewing OpenStudio 2.5. / En

2018-06-16 02:20:52 -0500 edited question How to utilize zone exhaust air for heatpump water heaters ?

How to utilize zone exhaust air for heatpump water heaters ? Modeliing a premise with very high internal heat gains such

2018-06-16 02:16:50 -0500 asked a question How to utilize zone exhaust air for heatpump water heaters ?

How to utilize zone exhaust air for heatpump water heaters ? Modeliing a premise with very high internal heat gains such

2018-06-15 05:26:59 -0500 commented question DView with incorrect variable descriptors

I am looking for the annual run results only, and the curves seem to be displayed correctly - it's only that the variabl

2018-06-14 13:07:01 -0500 asked a question DView with incorrect variable descriptors

DView with incorrect variable descriptors When opening DView (instead of ResultsViewer) for viewing OpenStudio 2.5. / En

2018-06-14 05:50:07 -0500 asked a question OpenStudio crashing with IDF import (Versions 2.1, 2.5)

OpenStudio crashing with IDF import (Versions 2.1, 2.5) When trying to import the IDF example file 1ZoneDataCenterCRAC_w

2018-06-14 02:22:14 -0500 commented answer campus wide building energy modeling

Any Updates since 2014 worth mentioning ?

2018-06-14 02:21:27 -0500 commented answer campus wide building energy modeling

Any Updates since 2014 ?

2018-06-13 11:58:06 -0500 asked a question How to combine CFD simulations with OpenStudio & EnergyPlus ?

How to combine CFD simulations with OpenStudio & EnergyPlus ? CFD simulations are often used for detailed airflow st

2017-12-23 03:17:52 -0500 received badge  Autobiographer
2017-11-07 11:06:24 -0500 commented answer Results Visualization: Viewdata measure for EnergyPlus output ?

I see following difficulties with your recommendation: (1) displaying viewdata-report.html outside of OpenStudio: Fir

2017-11-07 11:05:44 -0500 commented answer Results Visualization: Viewdata measure for EnergyPlus output ?

I see following difficulties with your recommendation: (1) displaying viewdata-report.html outside of OpenStudio: Fire

2017-10-03 13:08:50 -0500 commented answer Time series visualization tools?

Yes, I think, you can also create interactive charts in R (check R packages for it) For simple plots, it takes only a s

2017-10-03 13:08:03 -0500 commented answer Time series visualization tools?

Yes, I think, you can also create interactive charts in R (check R packages for it) For simple plots, it takes only a s

2017-10-03 03:46:24 -0500 answered a question Time series visualization tools?

I mostly use R programming language (see open source CRAN website for download): It is easy to read in csv output from

2017-09-06 06:10:30 -0500 asked a question HOW TO EMS with OpenStudio ?

HOW TO EMS with OpenStudio ? As M. Dahlhausen has pointed out in Question on Results Visualization, EMS can be run with