Chandan Sharma's profile - activity

2021-04-16 00:39:58 -0500 received badge  Famous Question (source)
2017-12-11 02:43:46 -0500 answered a question VAV reheat coil behaving unexpectedly and leading to unmet hours

VAV reheat coil undersizing in a known issue. One workaround could be to reduce Central Heating Design Supply Air Temper

2017-10-29 05:00:55 -0500 answered a question SQLite query through Python returns strange variable name

This is because strings retrieved from sqlite database are Unicode instead of UTF-8. Following changes should get rid of

2017-10-27 03:41:48 -0500 answered a question constant outdoor air change fraction in E+

In addition to @mdahlhausen suggestion above, take a look at ZoneVentilation:DesignFlowRate

2017-10-27 03:39:06 -0500 answered a question [E+] Difference between various ExternalInterface variables: in usage & fuctionality

Refer to InputOutput Reference for ExternalInterface:Schedule, ExternalInterface:Actuator and ExternalInterface:Variable

2017-10-27 03:35:15 -0500 edited question solve Error relating ChillerHeater in E+

solve Error relating ChillerHeater in E+ I made a idf file including ChillerHeater:Absoption:DirectFired. Error message

2017-10-27 03:34:59 -0500 answered a question solve Error relating ChillerHeater in E+

This one probably requires opening an E+ issue. For the similar condition, though severe error is issued for chiller typ

2017-10-23 22:17:53 -0500 edited answer Water Source Summary anomaly

From OutputReportTabular.cc, totalWater = totalOnsiteWater + gatherMains + StorageChange; where gatherMains = Water Sup

2017-10-23 13:03:51 -0500 commented answer Water Source Summary anomaly

Tried to add some more information as to what I think is happening. StarvedVDot calculation is missing in the WaterUse.c

2017-10-23 12:58:03 -0500 edited answer Water Source Summary anomaly

From OutputReportTabular.cc, totalWater = totalOnsiteWater + gatherMains + StorageChange; where gatherMains = Water Sup

2017-10-22 04:44:17 -0500 edited answer Water Source Summary anomaly

From OutputReportTabular.cc, totalWater = totalOnsiteWater + gatherMains + StorageChange; where gatherMains = Water Sup

2017-10-22 01:54:22 -0500 commented answer Water Source Summary anomaly

Searching for keyword Mains Water Volume and Mains Supply Water Volume, in InputOutput Reference will show other report

2017-10-20 13:38:29 -0500 edited answer IDFVersionUpdater using commandline

IDFVersionUpdater can convert multiple files at once using *.lst file. Refer to AuxiliaryPrograms.pdf and search for sec

2017-10-20 13:31:49 -0500 edited answer IDFVersionUpdater using commandline

IDFVersionUpdater can convert multiple files at once using .lst file. Refer to AuxiliaryPrograms.pdf and search for sect

2017-10-20 13:26:05 -0500 commented answer IDFVersionUpdater using commandline

Several months ago, I had to convert 100s of 90.1 reference files from v8.4 to v8.7. And IDFVersionUpdater has been of g

2017-10-20 08:11:24 -0500 commented answer IDFVersionUpdater using commandline

If all the file names are defined in lst file, IDFVersionUpdater should be run only once to convert all of them from 8.4

2017-10-20 06:56:53 -0500 answered a question Water Source Summary anomaly

From OutputReportTabular.cc, totalWater = totalOnsiteWater + gatherMains + StorageChange; where gatherMains = Water Sup

2017-10-19 23:49:37 -0500 answered a question IDFVersionUpdater using commandline

IDFVersionUpdater can convert multiple files at once using *.lst file. Refer to AuxiliaryPrograms.pdf and search for sec

2017-10-16 22:35:51 -0500 commented answer Have you added a dish station to your quick-serve restaurant? If so, how did you specify the equipment? i.e. definitions and schedules?

Unit of peak flow rate input is $m^3/s$ so it is independent of kitchen square footage. The area of kitchen in reference

2017-10-16 22:35:39 -0500 commented answer Have you added a dish station to your quick-serve restaurant? If so, how did you specify the equipment? i.e. definitions and schedules?

Unit of peak flow rate input is $$m^3/s$$ so it is independent of kitchen square footage. The area of kitchen in referen

2017-10-16 22:34:54 -0500 commented answer Have you added a dish station to your quick-serve restaurant? If so, how did you specify the equipment? i.e. definitions and schedules?

Unit of peak flow rate input is m^3/s so it is independent of kitchen square footage. The area of kitchen in reference f

2017-10-14 13:19:43 -0500 answered a question Have you added a dish station to your quick-serve restaurant? If so, how did you specify the equipment? i.e. definitions and schedules?

EnergyPlus example file RefBldgQuickServiceRestaurantNew2004_Chicago.idf can be referenced as shown below. WaterUse:E

2017-10-12 05:25:10 -0500 edited question fluid type in EnergyPlus

fluid type in EnergyPlus Hi! I want to make a plant loop consisting of WaterHeater:Mixed and Boiler:Steam. At PlantLoop

2017-10-12 05:23:38 -0500 answered a question fluid type in EnergyPlus

WaterHeater:Mixed and Boiler:Steam can not be on the same plant loop. Use and Source side nodes of WaterHeater:Mixed can

2017-10-11 18:32:23 -0500 received badge  Notable Question (source)
2017-10-09 01:28:21 -0500 edited answer How humidity is controled in HVACTemplate:System:VAV

Running simulation for one day of summer and winter each would show whether CoolReheat control is actually working or no

2017-10-09 01:26:03 -0500 answered a question How humidity is controled in HVACTemplate:System:VAV

Running simulation for one day of summer and winter each would show whether CoolReheat control is actually working or no

2017-10-07 00:58:18 -0500 answered a question EMS Actuator using nodal values

Erl variable names in EnergyManagementSystem:GlobalVariable object should not match with any other erl variable name. Ma

2017-10-01 01:59:25 -0500 answered a question primary-secondary heating

EnergyPlus PlantLoop object has input field Common Pipe Simulation which specifies a primary secondary configuration. Th

2017-09-27 13:08:36 -0500 answered a question Severe errors when "migrating" jeplus job from energyplus 8.5 to 8.7

Two new input fields are added in ZoneCapacitanceMultiplier:ResearchSpecialobject in v8.7. Original v8.5 idf should be t

2017-09-27 02:29:30 -0500 answered a question Outdoor Air Reset for Domestic Water Heater Supply Water Setpoint

A workaround is as follows: EnergyManagementSystem:Program, myTempManager, !- Name SET myTempControl=(-2/3)* Outd

2017-09-11 03:09:34 -0500 edited answer Zone Contaminant Source or Sink CO2 Gain seems to be wrong

Following code snippet shows how these output variables are calculated for ( Loop = 1; Loop <= TotCO2Gen; ++Loop

2017-09-11 03:06:14 -0500 answered a question Zone Contaminant Source or Sink CO2 Gain seems to be wrong

Following code snippet shows how these output variables are calculated for ( Loop = 1; Loop <= TotCO2Gen; ++Loop

2017-09-08 05:28:36 -0500 answered a question Calculating Power, Capacity, and COP from Chiller Curves

Reporting above outputs at detailed frequency as opposed to hourly would show better comparison. Available capacity is c

2017-07-23 10:06:29 -0500 answered a question How to generate the Chiller:Electric:ReformulatedEIR curves?

This link provides modified version of curve fit tool that comes with EnergyPlus installation. It can be used to generat

2017-07-20 22:24:18 -0500 commented answer How can I model SetpointManager:Warmest, with a variable Maximum Setpoint Temperature?

You are right. Warmest SPM sets zone air flow rate before EMS updates the setpoint. To accomplish your above goals, I wo

2017-07-20 05:19:22 -0500 answered a question How can I model SetpointManager:Warmest, with a variable Maximum Setpoint Temperature?

You probably have to write a combination of EMS and warmest SPM to get this working. Snippet below may provide some help

2017-06-09 15:02:37 -0500 received badge  Popular Question (source)
2017-03-20 06:59:31 -0500 commented question EnergyPlus schedules and daylight savings time

My understanding is that E+ applies daylight saving time when either of these conditions are met a) if epw file has Daylight Saving Start Date and Daylight Saving End Date in the line HOLIDAYS/DAYLIGHT SAVINGS and input field Use Weather File Daylight Saving Period in RunPeriod object in idf is set to Yes b) Or epw may not have daylight saving period but idf has RunPeriodControl:DaylightSavingTime object.

2017-02-17 03:18:46 -0500 commented question Error: ** Severe ** ProcessSurfaceVertices: Divider area exceeds glazed opening for window...

Divider area is calculated as follows.

DivArea = DivWidth * ( HorDividers * Surface.Width + VertDividers * Surface.Height - HorDividers * VertDividers * DivWidth );
DividerArea = DivArea * Surface.Multiplier;

Since Surface.Multiplier = 1, for HorDividers=0, VertDividers = 6, DivArea = 1.08 (as you correctly calculated). and for HorDividers=6, VertDividers = 0, DivArea = 23.4. (seems incorrect and is what E+ is calculating) Debugging idf with E+ source code or posting link to actual idf will help in seeing what is going on inside E+.

2016-12-16 06:01:02 -0500 commented question Trying to find a complete object list for E+

@NickC, This excel tool parses the Energy+.idd and print out all the objects along with their required input fields. I could only do limited testing so if you find any issue while using this tool, please do let me know. All objects and required input fields for E+ versions 7.2, 8.0, 8.1, 8.2, 8.3, 8.4, 8.5, and 8.6 are also in the spreadsheet. Looks like in v 8.6, "required-field" special comment is removed from a lot of input fields.

2016-12-15 19:43:50 -0500 commented question Trying to find a complete object list for E+

C:\EnergyPlusV8-5-0\ExampleFiles\ExampleFiles-ObjectsLink.html ? (same for 8.4 and 8.6.)

2016-12-06 20:42:16 -0500 commented question Temps differ for adjacent nodes
2016-12-02 20:43:05 -0500 received badge  Organizer (source)
2016-12-02 20:36:10 -0500 edited question Temps differ for adjacent nodes

Dear UMH folk, My EnergyPlus heating loop has two adjacent nodes that, in my mind, should have identical properties. One node is the supply side outlet node, the other is the demand side inlet node. I've confirmed via IDF review and SVG file that they are indeed adjacent ... but they have temperatures differing by several degrees C. That doesn't make sense to me.

Can one of you shed some light on why that might occur?

p.s., Simple, single hot water boiler loop with outdoor reset control image description image description

2016-12-02 20:35:23 -0500 answered a question Temps differ for adjacent nodes
2016-07-21 13:00:04 -0500 commented answer Default Condenser Loop Tower and Evaporative Fluid Cooler Design water flow rate

Refer to note in the idd for Nominal Capacity input filed in CoolingTower:SingleSpeed. It is TR and not THR. Catalog data shows 29-424 nominal tons for 87 to 1272 GPMs from simple 3 GPM/Ton rule. While 87GPM∗8.33BTU/gal∗60min/h∗10F/12000 give 36.24 (i.e. 29*1.25) and same is true for all other GPMs. The confusion here is because Nominal Capacity is thought as 36.24 Ton while EnergyPlus expects it as 29 Ton and 1.25 should specified in the input field in Heat Rejection Capacity and Nominal Capacity Sizing Ratio. Design tower load within E+ will then be calculated as 1.25 * 29 = 36.24.