I am a bit surprised but yes the min PLR for the VRF HP is hard wired at 0.25. That should be fixed.

 CALL CreateNewObj('AirConditioner:VariableRefrigerantFlow')
 CALL AddToObjStr('Minimum Heat Pump Part-Load Ratio','0.25')