You need to modify the schedule for HVAC Operation (HVACOperationSchd) as well as the heating and cooling setpoint temperature schedules. Did you modify the setpoint temperature schedules into a certain range?

In PNNL Prototype building models, there may be multiple schedules for heating and cooling temperature setpoint. Some of them may not be used. So you need to modify the schedules that are used.