Question-and-Answer Resource for the Building Energy Modeling Community
Get started with the Help page
Ask Your Question

Revision history [back]

click to hide/show revision 1
initial version

I've had the same problem with my heating loop. I Set the PlantLoop: Plant Loop Demand Calculation Scheme temperature setpoint to my loop design temperature and it get solve. I mean I'd set this setpoint at 60 deg and my boiler had been set on 82 deg. so I changed PlantLoop: Plant Loop Demand Calculation Scheme setpoint to 82 deg and it get solve.