In the tabular reports, I would start by looking at the Standard 62.1 Summary which will show for each system the Outdoor Air Intake Flow - Vot for heating and cooling and for each zone the need for outdoor air.

Outdoor air is also shown in the tabular reports in the Component Sizing Summary report under Controller:OutdoorAir and it will show the minimum and maximum (using economizer) outdoor air flow in m3/s or CFM for each system.

The use of SI or IP units can be set in the OutputControl:Table:Style object.