This answer suggests modifying the Timesteps in Averaging Window input in the SIzing:Parameters input to smooth out the spike in the load associated with recovering from a night setback/system off period.

I think if you maintain the averaging window to one hour you are within the intent of the generally accepted engineering standards referenced in G2.2.3.

This answer suggests modifying the Timesteps in Averaging Window input in the SIzing:Parameters input object to smooth out the spike in the load associated with recovering from a night setback/system off period.

I think if you maintain the averaging window to one hour you are within the intent of the generally accepted engineering standards referenced in G2.2.3.