2019-07-25 10:10:02 -0500 commented answer What is the best way to input elevator in OpenStudio to attend Apendix G 90.1?

@mldichter You can find the elevator schedule for different building types in ASHRAE 90.1-2007 User's Manual, pages G-39

2016-02-19 13:44:39 -0500 received badge  Teacher (source)
2016-02-03 20:03:57 -0500 answered a question What is the best way to input elevator in OpenStudio to attend Apendix G 90.1?

Here's how I do it. I model an elevator shaft as a single thermal zone (multiple spaces but one thermal zone). I attach to that zone an ElectricEquipment object with the rated power of the elevator and I use the elevator operation schedule from ASHRAE 90.1-1989 (also in ASHRAE 90.1-2007 User's Manual) for the building type being modelled (retail, office, etc.). I modify the schedule to fit the actual operation hours of the building.

And yes, this is necessary for App G of ASHRAE 90.1/LEED. The elevator energy use is considered as process energy.