2023-09-21 08:23:08 -0500 | answered a question | Is it possible to change the convective/radiant fraction of the idealloadsairsystem? As has been mentioned before, this is not possible, but you can achieve the same result by using a ZoneHVAC:Baseboard:Ra |
2023-07-28 07:41:42 -0500 | commented answer | How can I create an ideal radiant heating and/or cooling system ? Yes, that is exactly what I used before - but it is not a radiant cooling system. |
2023-07-26 10:42:27 -0500 | marked best answer | Radiative fraction of electric baseboard heater not included in baseboard's total heating rate Hello, Does anyone know, why the I am trying to model a single room exposed to a constant outdoor condition. For indoor heating I use an electric baseboard heater (operative temperature controlled), which allows me to specify the radiative fraction and distribute it to specific surfaces and people. I ensured that all fractions to people and surfaces sum up to unity:
Where for me Now: the output variables for the baseboard heating indicate the total electric consumed power, which is the same as the sum of the convective and the radiative fraction. From the I/O reference, I understood that the total heating rate should also be the sum of the two and with an efficiency of 1 equal to the electric power.
However, for me the output of the baseboard total heating rate is equal to the convective part only, leaving out the radiant fraction and is therefore also lower than the electricity rate. I tried changing the radiative fraction, which only changed the value of the Does anyone have an idea? Many thanks in advance - I am happy to provide more information if needed! Unfortunately I am new here and can not upload any files yet?! :/ |
2023-07-26 10:42:27 -0500 | received badge | ● Scholar (source) |
2023-07-26 10:39:08 -0500 | answered a question | How can I create an ideal radiant heating and/or cooling system ? Another easy way, if you are only interested in a radiant heating system, is to use the ZoneHVAC:Baseboard:RadiantConvec |
2023-07-25 09:38:23 -0500 | received badge | ● Student (source) |
2023-07-25 09:38:20 -0500 | received badge | ● Teacher (source) |
2023-07-25 09:30:41 -0500 | asked a question | Incomplete heat balance with CondFD and electric radiant/convective baseboard heater Incomplete heat balance with CondFD and electric radiant/convective baseboard heater The radiant fraction of an electric |
2023-07-25 09:30:36 -0500 | answered a question | Radiative fraction of electric baseboard heater not included in baseboard's total heating rate After some investigative simulations, reading the Engineering Reference and the I/O Reference multiple times, I realised |
2023-07-25 09:30:30 -0500 | edited question | Radiative fraction of electric baseboard heater not included in baseboard's total heating rate Radiative fraction of electric baseboard heater not included in baseboard's total heating rate Hello, I am trying to mo |
2023-07-20 09:06:24 -0500 | commented answer | How to set deadband of themostat setpoint Ah, I see! Many thanks!🙏 |
2023-07-19 16:36:31 -0500 | commented answer | How to set deadband of themostat setpoint @Aaron Boranian great explanation, but I wonder how to input the optional field Temperature Difference Between Cutout An |
2023-07-19 05:37:44 -0500 | received badge | ● Supporter (source) |
2023-07-18 12:03:00 -0500 | commented question | Radiative fraction of electric baseboard heater not included in baseboard's total heating rate Thanks @Aaron Boranian, here the link to the idf and used epw: IDF epw |
2023-07-18 10:21:54 -0500 | asked a question | Radiative fraction of electric baseboard heater not included in baseboard's total heating rate Radiative fraction of electric baseboard heater not included in baseboard's total heating rate Hello, I am trying to mo |