2022-07-28 05:38:13 -0500 marked best answer EnergyPlus simulation failed after version converting

Dear all, I updated the mid-rise apartment prototype model from DOE website from version 8.0 to version 9.1. After that, when I run the model, I got severe errors like:

   ** Severe  ** checkSubSurfAzTiltNorm: Outward facing angle of subsurface differs more than 90.0 degrees from base surface.
   **   ~~~   ** Subsurface="TWINDOW14" Tilt = 90.0  Azimuth = 270.0
   **   ~~~   ** Base surface="T EWALL C" Tilt = 90.0  Azimuth = 90.0

image description

Please let me know if you have any suggestions. Thank you

2020-03-23 10:49:39 -0500 edited question Baseline Return Air Path

Baseline Return Air Path Dear all, I need your opinion regarding how to decide the return air path for the baseline mod

2020-02-18 15:55:52 -0500 asked a question Baseline Return Air Path

Baseline Return Air Path Dear all, I need your opinion regarding how to decide the return air path for the baseline mod

2020-01-27 18:33:44 -0500 edited question ------------------------

IES model thermal block question Dear all, I need your professional opinion for the question I have. Attached picture is

2020-01-27 17:58:55 -0500 asked a question ------------------------

IES model thermal block question Dear all, I need your professional opinion for the question I have. Attached picture is

2020-01-24 11:04:22 -0500 edited question ----------------------

Relative Humidity for the Baseline Model

2020-01-24 11:04:13 -0500 edited question ----------------------

Relative Humidity for the Baseline Model

2020-01-19 12:07:39 -0500 received badge  Teacher (source)
2020-01-16 11:07:20 -0500 marked best answer Baseline HVAC system

For the 5 floors office building

2020-01-15 17:35:11 -0500 edited answer LPD Space-by-Space Method v.s. Building Area Method

Per ASHRAE 90.1-2016 and ASHRAE 90.1-2019, only space by space method mentioned that can be used for the baseline model.

2020-01-15 17:33:52 -0500 edited answer LPD Space-by-Space Method v.s. Building Area Method

Per ASHRAE 90.1-2016 and ASHRAE 90.1-2019, only space by space method mentioned that can be used for the baseline model.

2020-01-15 17:32:26 -0500 edited answer LPD Space-by-Space Method v.s. Building Area Method

Per ASHRAE 90.1-2016 and ASHRAE 90.1-2019, only space by space method mentioned that can be used for the baseline model.

2020-01-15 17:30:50 -0500 commented answer regulated energy & unregulated energy

Thank you Pajordan

2020-01-15 17:30:33 -0500 marked best answer regulated energy & unregulated energy

Hello everyone, I have a question regarding regulated energy and unregulated energy. Per ASHRAE 90.1-2016, the baseline model for each code year is calculated based on baseline regulated energy cost, baseline unregulated energy cost, baseline performance cost and building performance factor. My question is does the baseline unregulated energy cost should be the same as the proposed building performance cost? Is that the reason why the building performance factor only multiplying with the regulated energy cost but not with the unregulated energy cost

2020-01-13 16:45:04 -0500 asked a question regulated energy & unregulated energy

regulated energy & unregulated energy Hello everyone, I have a question regarding regulated energy and unregulated e

2020-01-13 11:06:44 -0500 marked best answer LPD Space-by-Space Method v.s. Building Area Method

Dear all, I have a question regarding LPD space-by-space method v.s LPD building area method. I would like to know if I use the space-by-space method for the baseline model, do I have to use the space-by-space method for the proposed model or it doesn't matter. This means I can use the space-by-space method for the baseline model but use the building area method for the proposed model. Thank you!

2020-01-13 11:06:44 -0500 received badge  Scholar (source)
2020-01-13 11:05:48 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

I found the certain answer from LEED 4.1 as well. "Baseline: All building spaces area modeled using the Space-by-Space

2020-01-13 11:05:41 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

I found the certain answer from LEED 4.1 as well. "Baseline: All building spaces area modeled using the Space-by-Space

2020-01-13 11:05:18 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

I found the certain answer from LEED 4.1 as well. "All building spaces area modeled using the Space-by-Space Method. (P

2020-01-13 10:56:43 -0500 commented question LPD Space-by-Space Method v.s. Building Area Method

It has been moved

2020-01-13 10:55:24 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

Thank you for mentioning this reference "https://www.pnnl.gov/main/publications/external/technical_reports/PNNL-26917.pd

2020-01-13 10:53:52 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

Thank you for mentioning this reference "https://www.pnnl.gov/main/publications/external/technical_reports/PNNL-26917.pd

2020-01-13 10:53:21 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

Follow the previous comment. I think your comment is correct if only under this condition: If the space types are known

2020-01-13 10:45:36 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

Thank you for pointing this reference "https://www.pnnl.gov/main/publications/external/technical_reports/PNNL-26917.pdf"

2020-01-07 16:06:25 -0500 answered a question LPD Space-by-Space Method v.s. Building Area Method

Per ASHRAE 90.1-2016 and ASHRAE 90.1-2019, only space by space method mentioned that can be used for the baseline model.

2020-01-03 09:29:40 -0500 commented question LPD Space-by-Space Method v.s. Building Area Method

Per ASHRAE 90.1-2016 and ASHRAE 90.1-2019, only space by space method mentioned that can be used for the baseline model.

2020-01-03 09:29:40 -0500 received badge  Commentator
2020-01-02 15:23:08 -0500 received badge  Critic (source)
2020-01-02 12:31:17 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

Yeah, I found this sentence as well, but G1.2.1 only talking about proposed model. If you go 2016 G3.1 No.6, it mention

2020-01-02 12:11:17 -0500 commented answer LPD Space-by-Space Method v.s. Building Area Method

What about ASHRAE90.1-2019. Per Table G3.1 No.6, it seems only Space-by-Space method can be used for the baseline model

2019-12-31 14:18:58 -0500 answered a question Different temperatures variations for different time steps

From my understanding, simulation time step means how frequent the system does the calculation in one hour (one hour her

2019-12-31 14:04:06 -0500 asked a question LPD Space-by-Space Method v.s. Building Area Method

LPD Space-by-Space Method v.s. Building Area Method Dear all, I have a question regarding LPD space-by-space method v.s

2019-11-27 16:27:07 -0500 commented question use one fan equivalent to multiple fans

Besides the comment above, I think it depends on if all these fans have the same schedule as well. But if you need to c

2019-11-27 16:26:52 -0500 commented question use one fan equivalent to multiple fans

Besides the comment above, I think it depends on if all these fans have same schedule as well. But if you need to calib