2014-12-28 12:14:30 -0500 asked a question Unsure about autosizing results

If I use only one coil in the system and I would like it to be autosize. Am I doing it right there I am not very sure. image description image description

Coil:Cooling:DX:TwoStageWithHumidityControlMode,
DOAS Cooling Coil, !- Name
HVACTemplate-Always 1, !- Availability Schedule Name
DOAS Supply Fan Outlet, !- Air Inlet Node Name
DOAS Cooling Coil Outlet,!- Air Outlet Node Name
, !- Crankcase Heater Capacity {W}
, !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
1, !- Number of Capacity Stages
0, !- Number of Enhanced Dehumidification Modes
CoilPerformance:DX:Cooling, !- Normal Mode Stage 1 Coil Performance Object Type
DOAS Standard Perf 1, !- Normal Mode Stage 1 Coil Performance Name
CoilPerformance:DX:Cooling, !- Normal Mode Stage 1+2 Coil Performance Object Type
DOAS Standard Perf 1+2; !- Normal Mode Stage 1+2 Coil Performance Name


Sizing:System,
DOAS, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1.0, !- Minimum System Air Flow Ratio
2, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
16, !- Central Cooling Design Supply Air Temperature {C}
12.2, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Sizing Option
Yes, !- 100% Outdoor Air in Cooling
Yes, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.003, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
ZoneSum; !- System Outdoor Air Method

But Design Load is 76kW already but my coil only has 46kW

One more question is that in the Sizing:System I dont have any precool or preheat in the outdoor airduct what should I input there

2014-12-22 13:15:36 -0500 asked a question DOAS input Problem

I have started my simulation and It shows the following warning and I am not sure what is it and what to do about it. I have trying to set up a DOAS System

DOAS System

Schematics

First of all, I am not very sure what are these errors come from and how can I solve it?

** Warning ** SimHVAC: Maximum iterations (20) exceeded for all HVAC loops, at HONG KONG SAR CHN CityUHK-45007 WMO#=450070, 01/01 03:15 - 03:30
**   ~~~   ** The solution for one or more of the Air Loop HVAC systems did not appear to converge   
**   ~~~   ** Air System Named = DOAS did not converge for mass flow rate   
**   ~~~   ** Check values should be zero. Most Recent values listed first.
**   ~~~   ** Demand-to-Supply interface mass flow rate check value iteration history trace:
0.421904,0.571668,0.774595,1.049554,1.422117,4.239839,0.421904,0.571668,0.774595,1.049554,
**   ~~~   ** Supply-to-demand interface deck 1 mass flow rate check value iteration history trace:
0.421904,0.571668,0.774595,1.049554,1.422117,0.311375,0.421904,0.571668,0.774595,1.049554,
**   ~~~   ** Air System Named = DOAS did not converge for temperature
** ~~~   ** Check values should be zero. Most Recent values listed first.
** ~~~   ** Demand-to-Supply interface temperature check value iteration history trace:
3.462632E-002,2.555499E-002,1.886016E-002,1.391922E-002,1.027269E-002,0.103233,3.462632E-002,2.555499E-002,1.886016E-002,1.391922E-002,
**   ~~~   ** Supply-to-demand interface deck 1 temperature check value iteration history trace:
2.555499E-002,1.886016E-002,1.391922E-002,1.027269E-002,0.103233,3.462632E-002,2.555499E-002,1.886016E-002,1.391922E-002,1.027269E-002,
**   ~~~   ** Air System Named = DOAS did not converge for energy
**   ~~~   ** Check values should be zero. Most Recent values listed first.
** ~~~   ** Demand-to-Supply interface energy check value iteration history trace:  9612.881052,13025.189533,17648.773708,23913.603146,32402.274792,96602.722233,9612.881052,13025.189533,17648.773708,23913.603146,
**   ~~~   ** Supply-to-demand interface deck 1 energy check value iteration history trace: -9612.881052,-13025.189533,-17648.773708,-23913.603146,-33006.735202,-7094.521112,-9612.881052,-13025.189533,-17648.773708,-23913.603146,

My next warnings are the following. As This is a DOAS System I am not sure how to adjust the input to Energyplus

Yes, !- Use Outdoor Air DX Cooling Coil
7.2; !- Outdoor Air DX Cooling Coil Leaving Minimum Air Temperature {C}

The maximum Outdoor Air DX Cooling Coil Leaving Minimum Air Temperature is 7.2C But What If my leaving air temperature is larger than 7.2? Can it still be a DOAS Coil?

   ** Warning ** CalcDoe2DXCoil: Coil:Cooling:DX:SingleSpeed "DOAS COOLING COIL 1" - Full load outlet air dry-bulb temperature < 2C. This indicates the possibility of coil frost/freeze. Outlet temperature = -1.12 C.
   **   ~~~   **  ...Occurrence info = HONG KONG SAR CHN CityUHK-45007 WMO#=450070, 01/02 08:00 - 08:04
   **   ~~~   ** ... Possible reasons for low outlet air dry-bulb temperatures are: This DX coil
   **   ~~~   **    1) may have a low inlet air dry-bulb temperature. Inlet air temperature = 16.701 C.
   **   ~~~   **    2) may have a low air flow rate per watt of cooling capacity. Check inputs.
   **   ~~~   **    3) is used as part of ...
(more)