Without getting into too much detail, the BEopt HVAC options currently require a lot of detailed inputs to determine the efficiency of the equipment in the EnergyPlus simulation. EER/COP inputs are indeed used in conjunction with SEER/HSPF, rated fan power, etc. You can see how the EnergyPlus inputs change when you vary the BEopt inputs.

We recognize that these inputs can be very challenging for a user to obtain and make it hard to create new BEopt options. With BEopt v3 (beta to be released in mid-December), we are greatly reducing the number/complexity of inputs required.

For example, an air conditioner in BEopt v2 requires:

  • Number of Speeds
  • Rated SEER
  • Installed SEER
  • EER(s)
  • Rated SHR(s)
  • Capacity Ratio(s)
  • Fan Speed Ratio(s)
  • Rated Fan Power
  • Installed Fan Power
  • Crankcase Power/Temperature

In BEopt v3, the only required inputs will be:

  • Number of Speeds
  • Rated SEER
  • Rated SHR
  • Fan Power (can be defaulted)