Maybe it's because the cooling towers are not achieving the entering condenser water temperatures at the PLRs in that table? It looks like the condenser water is using SetpointManager:FollowOutdoorAirTemperature, which may not achieve the entering CW temperatures listed in your Excel calculation at the respective PLRs.