It sounds like your goal is:

  1. Account for exhaust fan (EF) energy
  2. Let EnergyPlus know that air is moving from one zone to another

I've been using E+ for ~15 years, but have not explored the airflow network, so I can't help specifically with that. If I were doing this, I would:

  • Make a simple air loop with only outdoor air in the amount of ambient air you desire (or assign proper outdoor air to an existing air loop)
  • Add a Zone EF to exhaust that air
  • add an electric load in the transfer zone downstream of the exhaust fan equivalent to the fan's power (both zones)
  • add a ZoneMixing or ZoneCrossMixing object with the same airflow as the transfer airflow.