You might be getting forced by the min flow fraction at the terminal unit(s) (assuming you're using AirTerminal:SingleDuct:VAV:NoReheat). I would check there first.

Also, if you have an OA branch on your airloop (and people in your zone), flow might be getting forced in DesignSpecification:OutdoorAir which has a default value for outdoor_air_flow_per_person.