click to hide/show revision 1
initial version

The answer to this turned out to be a simple one. I didn't realize that when choosing the MutliSpeedFan control option in the Four Pipe Fan Coil object, that the 'Supply Air Fan Operating Mode Schedule Name' input become relevant and defaults to always 0 (cycling). Choosing a schedule that is Always 1 in this field produced the exact result I was looking for, and the fan no longer cycles off.