Question-and-Answer Resource for the Building Energy Modeling Community
Get started with the Help page
Ask Your Question

Revision history [back]

You need to input the calculated COP (remove the supply fan energy per ASHRAE 90.1-2013 G3.1.2.1) to the "Rated COP" in the OpenStudio. The Rated COP of OpenStudio is Gross Rated Cooling COP in the EnergyPlus.

Rated COP (Gross Rated Cooling COP) on OpenStudio input = Nominal Efficiency on Cooling Coils output report table > Standard Rated Net COP on DX Cooling Coils output report table