There are a couple report variables that can be used for this purpose.
Output:Variable,*,Air System Simulation Maximum Iteration Count,Detailed;
Output:Variable,*,Air System Simulation Iteration Count,Detailed;
Output:Variable,*,Air System Component Model Simulation Calls,Detailed;
The warnings will typically have a timestamp of the first occurance. To minimize the amount of information reported to the err file, warnings are summarized at the end of the simulation to report the number of times they occurred and the range of values a specific parameter had when the warning occurs.