The single-zone building has a >> 1,000 kBtu/sf EUI. You aren't seeing a large % change in cooling energy use, because your heating and fan energy use is so high. This is because the model assumes a 1,271 cfm/person ventilation rate in your Design Specification Outdoor Air. Typical values are ~20 cfm/person.

Also, the model has both Milan and New Delhi design days. Remove New Delhi design days.