I have rectified the problem my self.

  • The problem was related to the sizing factors. I gave a global sizing factor of 1.25 for cooling equipment as well as 1.25 for chiller. This made the chiller having more wattage than the cooling tower.

  • The comfort parameters are satisfied after I changed the default setting (like loop exit temperature and loop temperature difference)about condenser and chiller loops in open studio.