Looking at the hourly output for the chiller and the pumps, the condenser pump only runs when the chiller operates, which does happen throughout the year. The chiller (Chiller:Electric:EIR) condenser flow rate is the full flow rate whenever the chiller operates, regardless of load.

I have posted new issue 7111 to fix this or add a new option if there is a reason to keep this mode (variable evaporator flow with constant condenser flow).

Reference helpdesk ticket 13133.