The Reduce Ventilation By Percentage measure only modifies Outdoor Air Flow per Person, Outdoor Air Flow per Floor Area, and Outdoor Air Flow Air Changes per Hour based on lines 202-204 of the measure. I see that in your Design Specification Outdoor Air object you have 0 for each of those as you have defined your flow rate as a fixed flow rate.