The Reduce Ventilation By Percentage
measure only modifies Outdoor Air Flow per Person
, Outdoor Air Flow per Floor Area
, and Outdoor Air Flow Air Changes per Hour
based on lines 202-204 of the measure. I see that in your Design Specification Outdoor Air
object you have 0 for each of those as you have defined your flow rate as a fixed flow rate.