It looks like you have both the "Heating Design Air Flow Rate" and "Heating Maximum Air Flow" input fields of your zone sizing object set to 225 cfm. This would cause your Design Size Maximum Flow Fraction during Reheat of 1.00000 warning message. Try changing the "Heating Design Air Flow Rate" to 450 cfm to address the warning.