The OpenStudio Results are produced by a measure that gets values from the EnergyPlus results, so check there for the real values, specifically the Pumps table in the Equipment Summary report.

It looks like the measure is using the ratedFlowRate method here and here instead of the ratedPowerConsumption method. It also looks like the source_units and target_units variables are incorrect.

FYI @David goldwasser