Question-and-Answer Resource for the Building Energy Modeling Community
Get started with the Help page
Ask Your Question

Revision history [back]

click to hide/show revision 1
initial version

Maybe the ISO 13790 can help you to decide. "In particular you have not to dived a space in more thermal zone if 1. Set-point temperatures for heatingcooling of the spaces differ by no more than 4 K; 2. The spaces is serviced by the same heating systeme (if any) and the same cooling system (if any); 3. At least 80% of the floor area are serviced by the same ventilation system; 4. The ammount of ventilation (in cubic metre per square metre of floor area per second) differs by not more than a factor of 4 within 80% of the floor area."

Maybe the ISO 13790 can help you to decide. "In decide.

"*In particular you have not to dived a space in more thermal zone if 1. if

  1. Set-point temperatures for heatingcooling of the spaces differ by no more than 4 K; 2. K;

  2. The spaces is serviced by the same heating systeme (if any) and the same cooling system (if any); 3. any);

  3. At least 80% of the floor area are serviced by the same ventilation system; 4. system;

  4. The ammount of ventilation (in cubic metre per square metre of floor area per second) differs by not more than a factor of 4 within 80% of the floor area."area.*"

Maybe the ISO 13790 can help you to decide.

"*In particular you have not to dived a space in more thermal zone ifif:

  1. Set-point temperatures for heatingcooling of the spaces differ by no more than 4 K;

  2. The spaces is serviced by the same heating systeme (if any) and the same cooling system (if any);

  3. At least 80% of the floor area are serviced by the same ventilation system;

  4. The ammount of ventilation (in cubic metre per square metre of floor area per second) differs by not more than a factor of 4 within 80% of the floor area.*"

Maybe the ISO 13790 can help you to decide.

"*In "In particular you have not to dived a space in more thermal zone if:

  1. Set-point temperatures for heatingcooling of the spaces differ by no more than 4 K;

  2. The spaces is serviced by the same heating systeme (if any) and the same cooling system (if any);

  3. At least 80% of the floor area are serviced by the same ventilation system;

  4. The ammount of ventilation (in cubic metre per square metre of floor area per second) differs by not more than a factor of 4 within 80% of the floor area.*"area."