Maybe the ISO 13790 can help you to decide. "In particular you have not to dived a space in more thermal zone if 1. Set-point temperatures for heatingcooling of the spaces differ by no more than 4 K; 2. The spaces is serviced by the same heating systeme (if any) and the same cooling system (if any); 3. At least 80% of the floor area are serviced by the same ventilation system; 4. The ammount of ventilation (in cubic metre per square metre of floor area per second) differs by not more than a factor of 4 within 80% of the floor area."
2 | No.2 Revision |
Maybe the ISO 13790 can help you to decide.
"In decide.
"*In particular you have not to dived a space in more thermal zone if
1. if
Set-point temperatures for heatingcooling of the spaces differ by no more than 4 K;
2. K;
The spaces is serviced by the same heating systeme (if any) and the same cooling system (if any);
3. any);
At least 80% of the floor area are serviced by the same ventilation system;
4. system;
The ammount of ventilation (in cubic metre per square metre of floor area per second) differs by not more than a factor of 4 within 80% of the floor area."area.*"
3 | No.3 Revision |
Maybe the ISO 13790 can help you to decide.
"*In particular you have not to dived a space in more thermal zone ifif:
Set-point temperatures for heatingcooling of the spaces differ by no more than 4 K;
The spaces is serviced by the same heating systeme (if any) and the same cooling system (if any);
At least 80% of the floor area are serviced by the same ventilation system;
The ammount of ventilation (in cubic metre per square metre of floor area per second) differs by not more than a factor of 4 within 80% of the floor area.*"
4 | No.4 Revision |
Maybe the ISO 13790 can help you to decide.
"*In "In particular you have not to dived a space in more thermal zone if:
Set-point temperatures for heatingcooling of the spaces differ by no more than 4 K;
The spaces is serviced by the same heating systeme (if any) and the same cooling system (if any);
At least 80% of the floor area are serviced by the same ventilation system;
The ammount of ventilation (in cubic metre per square metre of floor area per second) differs by not more than a factor of 4 within 80% of the floor area.*"area."