@rraustad , Thank you for your guidance. I seem to have finally solved this issue. I had been looking at all the inputs related to the heating systems for the past couple of days except the design flow rates of the absorption chiller component. I had autosized the hot water, chilled water and condenser water inputs for the ChillerHeater:Absorption:DirectFired which E+ didn't like. I entered numeric values for the design flow rates for this component and the results tables now display numeric values.
https://dl.dropboxusercontent.com/u/5148496/FinalSiteEnergy.JPG
Thank you once again for your help!
Thanks, Raghu