If you have VAV terminals, you can use the terminal's local control for outdoor air with the DesignSpecification:OutdoorAir setup for DCV. Of course there can only be one OA fraction for the air handler so this will really adjust the damper minimum stop for DCV zones. You'll want to use the DesignSpecification:OutdoorAir for the non-DCV zones as well for a fair comparison.