There is no way to do this with native controllers. EnergyPlus does not have the notion of separate critical circuits.

What you could do is use EMS. Monitor the state of charge with an EMS Sensor. Then override availability schedules and the like to shut down those components and systems that are not critical when the state of charge drops too low.