A simple reason for your unexplained temperature fluctuations may be that Chiller outlet node temperature will typically deviate from setpoint temperatures during times when Chiller is not operating, i.e. whenever Chiller outlet node mass flow rate is zero. You can check this immediately by looking at temperatures and mass flow rates simultaneously in ResultsViewer.