| 1 | initial version |
Hi, I also ran into this warning when using a TMYx 2011-2025 EPW file from climate.onebuilding.org. But it looks to me like the file does have design conditions on the second line, like the TMY3's do! It even says in column 3 it's from ASHRAE Handbook 2025. It looks like in the TMY3 the word "heating" occurs in row 2 column 5, but in the TMYx the word "heating" occurs in row 2 column 4. There's an extra blank field in the TMY3.
TMYx, Buffalo Niagara: row 2, first 7 fields
DESIGN CONDITIONS 1 2025 ASHRAE Handbook -- Fundamentals - Chapter 14 Climatic Design Information Heating 1 -15.9 -13.5
TMY3, Chicago Ohare: row2, first 7 fields
DESIGN CONDITIONS 1 Climate Design Data 2009 ASHRAE Handbook Heating 1 -20