2022-11-02 07:44:40 -0500 | received badge | ● Rapid Responder (source) |
2022-11-02 07:44:40 -0500 | answered a question | eQUEST Abnormal Simulation Results Error My first suggestion if you haven't done so already is to create heating and cooling design days. Can you share the .inp |
2022-01-05 23:09:36 -0500 | answered a question | Peak cooling load - equest If you leave your circulation loop sizing as the default "secondary" then it adds up all of the maximum coil loads at fu |
2021-11-06 11:17:03 -0500 | commented answer | how to model Window with the right Uvalue in equest When I run a glass type 2004 with a thermally broken frame (eQUEST entered frame conductance U-value of 1.245 BTU/hr-ft2 |
2021-11-06 10:37:36 -0500 | received badge | ● Rapid Responder (source) |
2021-11-06 10:37:36 -0500 | answered a question | how I can create two different schedule for DHW in equest ? DHW is on the waterside tab. DHW loads are created as direct process loads on a DHW loop. You can create up to 10 diff |
2021-10-23 07:16:15 -0500 | answered a question | how to model Window with the right Uvalue in equest If you are modelling glazing using an entry from the glass library then you do indeed have to also enter a frame width a |
2021-01-11 17:36:59 -0500 | received badge | ● Teacher (source) |
2020-12-22 10:14:50 -0500 | answered a question | What's the correct way to model central air-to-water heat pump with backup electric boiler and hydronic baseboards? Using a chiller of type Heat Pump forces you to use the loop type 2-pipe as that defines whether the heat pump is in hea |
2015-03-03 08:42:50 -0500 | received badge | ● Supporter (source) |