First time here? Check out the Help page!
2022-06-12 11:10:20 -0500 | received badge | ● Popular Question (source) |
2022-05-18 09:37:06 -0500 | received badge | ● Teacher (source) |
2022-05-18 07:26:52 -0500 | edited answer | Different values of "Output:Variable" and "EnergyManagementSystem:OutputVariable" for the same Sensor in EnergyPlus Thanks to @JasonGlazer and @Denis Bourgeois, EMS output is simply lagging behind every timestep that can be due to repor |
2022-05-18 07:26:09 -0500 | marked best answer | Different values of "Output:Variable" and "EnergyManagementSystem:OutputVariable" for the same Sensor in EnergyPlus I am using EMS to compute an intermediate value based on the available sensors. To check that the correct values are used in the EMS calculations, I created customized EMS outputs for those sensors and compared them with their values produced in the ESO file. For example, one of the sensors is the System Node Wetbulb Temperature of the Air Loop Demand Side Outlet as follows:
Is there a way to eliminate or minimize this error? I tried different EMS Program Calling options as follows: Thank you. |
2022-05-18 07:25:54 -0500 | answered a question | Different values of "Output:Variable" and "EnergyManagementSystem:OutputVariable" for the same Sensor in EnergyPlus Thanks to @JasonGlazer and @Denis Bourgeois, EMS output is simply lagging behind every timestep that can be due to repor |
2022-05-18 07:25:54 -0500 | received badge | ● Rapid Responder (source) |
2022-05-18 07:21:13 -0500 | commented question | Different values of "Output:Variable" and "EnergyManagementSystem:OutputVariable" for the same Sensor in EnergyPlus Thank you @JasonGlazer and @Denis Bourgeois for your reply. Indeed, I have missed this observation because my question |
2022-05-18 06:20:08 -0500 | edited question | Custom Control of AHU using EMS in Energy Plus Custom Control of AHU using EMS in Energy Plus I want to design a customized control logic for a CAV AHU in E+ that cont |
2022-05-18 06:19:09 -0500 | edited question | Custom Control of AHU using EMS in Energy Plus Custom Control of AHU using EMS in Energy Plus I want to design a customized control logic for a CAV AHU in E+ that cont |
2022-05-18 04:30:10 -0500 | asked a question | Different values of "Output:Variable" and "EnergyManagementSystem:OutputVariable" for the same Sensor in EnergyPlus Different values of "Output:Variable" and "EnergyManagementSystem:OutputVariable" for the same Sensor in EnergyPlus I am |
2022-05-18 03:38:24 -0500 | edited question | Custom Control of AHU using EMS in Energy Plus Custom Control of AHU using EMS in Energy Plus I want to design a customized control logic for a CAV AHU in E+ that cont |
2022-05-18 03:36:29 -0500 | asked a question | Custom Control of AHU using EMS in Energy Plus Custom Control of AHU using EMS in Energy Plus I want to design a customized control logic for a CAV AHU in E+ that cont |
2022-05-18 03:36:25 -0500 | asked a question | Custom Control of AHU using EMS in Energy Plus Custom Control of AHU using EMS in Energy Plus I want to design a customized control logic for a CAV AHU in E+ that cont |
2022-05-11 04:58:39 -0500 | commented answer | Design and Settings of AirFlowNetwork model in E+ for large space served by multiple AHUs Thank you for your reply and help. This is very useful! |
2022-05-11 04:58:08 -0500 | marked best answer | Design and Settings of AirFlowNetwork model in E+ for large space served by multiple AHUs I am attempting to model an AirFlowNetwork in E+ as presented in my previous question: Interzone airflow between adjacent zones with open walls and dedicated AHUs, and I have some doubts I would like your help to clear out, which are:
Thank you. |
2022-05-10 03:48:43 -0500 | asked a question | Design and Settings of AirFlowNetwork model in E+ for large space served by multiple AHUs Design and Settings of AirFlowNetwork model in E+ for large space served by multiple AHUs I am attempting to model an Ai |
2022-04-12 00:31:08 -0500 | marked best answer | Interzone airflow between adjacent zones with open walls and dedicated AHUs I am simulating a large theater with multiple levels (vertically) and with an opening in the roof that makes about 30% of the roof area. The theater is served by multiple AHUs. I have divided the large space into subspaces (Zones) based on AHUs' serving areas, such that each Zone is served by an AHU. I created opening surfaces between the adjacent zones (can be horizontal and vertical based on the Zone location relative to adjacent ones). I want to model the interflow between the zones - given mechanical ventilation - that closely represents the real life scenario. I have experimented with both AirFlowNetwork model and the ZoneMixing and the results of the two are different. I read that AirFlowNetwork model is more complex and detailed, yet it does not work/provide accurate results for some scenarios (e.g., Air circulation and/or air temperature stratification within a thermal zone.). I could not decide which is representative, sufficient, and reliable to use for my case. Given my limited expertise with Energy+, I would like to ask if I should use AirFlowNetwork model or ZoneMixing will be sufficient for this application. Additionally, I would appreciate any feedback, ideas, or suggestion regarding my request. * UPDATE * Based on @Jason DeGraw's answer, I would like to ask if my strategy to approach this is reasonable. If ZoneMixing is used, I will need to include ZoneMixing objects in both directions in order to insure mass balance, correct? For example, assuming that Zone 1 and Zone 2 only interact which each other, I should have the following because ZoneMixing statement only affects the energy balance of the “receiving” zone and does not produce any effect on the “source” zone (Source: https://bigladdersoftware.com/epx/doc...). Hence, complementary mixing statements of zones with air exchange should be included while having Delta Temperature set to 0 in order for mixing to occur regardless of the relative zone temperatures. Under the assumptions that (1) the HVAC system design insures thermal comfort, and (2) the paths of air exchange between zone are independent of the AHU's supply-return air paths, I am thinking of using the air velocity thermal comfort requirements (which is I think is a maximum of 2 m/s) knowing the cross-section area between the zones and air density to set the maximum air exchange rates between the zones (i.e., Design Level). Kindly let me ... (more) |
2022-04-12 00:31:08 -0500 | received badge | ● Scholar (source) |
2022-04-07 02:09:59 -0500 | edited question | Interzone airflow between adjacent zones with open walls and dedicated AHUs Interzone airflow between adjacent zones with open walls and dedicated AHUs I am simulating a large theater with multipl |
2022-04-06 09:21:12 -0500 | received badge | ● Student (source) |
2022-04-06 09:15:25 -0500 | commented answer | Interzone airflow between adjacent zones with open walls and dedicated AHUs Thank you Jason for your reply. I have already conducted a CFD analysis to identify air paths. I do not have enough info |
2022-04-06 03:08:42 -0500 | received badge | ● Supporter (source) |
2022-04-06 03:05:43 -0500 | received badge | ● Editor (source) |
2022-04-05 08:43:32 -0500 | edited question | Interzone airflow between adjacent zones with open walls and dedicated AHUs Interzone airflow between adjacent zones with open walls and dedicated AHUs I am simulating a large theater with multipl |
2022-04-04 08:35:52 -0500 | asked a question | Interzone airflow between adjacent zones with open walls and dedicated AHUs Interzone airflow between adjacent zones with open walls and dedicated AHUs I am simulating a large theater with multipl |