2018-01-07 00:49:34 -0500 | commented answer | Equipment sizing errors Thank you! You've been very helpful. |
2018-01-07 00:49:11 -0500 | marked best answer | Equipment sizing errors I have an HVAC system consisting of 2 parallel air-cooled chillers, each with a designated pump. For each of the pumps I assigned flow rate of 15 kg/s . On each of the chillers I specified Reference Chilled Water Flow Rate of 15 kg/s and Condenser Fluid Rate of 15.234 m3/h. Also, on the water cooling coil I put 15 kg/s on the Design Water Flow rate and Design Air Flow Rate of 4.342 m3/h. However, I receive the following errors: Water cooling coil: * ~~~ * User-Specified Design Air Flow Rate [m3/s] = 4.34200 * ~~~ * differs from Design Size Design Air Flow Rate [m3/s] = 4.87859 User-Specified Design Water Flow Rate [m3/s] = 1.50000E-002 * ~~~ * differs from Design Size Design Water Flow Rate [m3/s] = 1.02900E-002 * ~~~ * This may, or may not, indicate mismatched component sizes. For both chillers: *** SizeChillerElectricEIR: Potential issue with equipment sizing for CHILLER - AIR COOLED 1 * ~~~ * User-Specified Reference Chilled Water Flow Rate of 1.50000E-002 [m3/s] * ~~~ * differs from Design Size Reference Chilled Water Flow Rate of 3.00000E-002 [m3/s] * ~~~ * This may, or may not, indicate mismatched component sizes. * ~~~ * Verify that the value entered is intended and is consistent with other components. *** SizeElectricEIRChiller: Potential issue with equipment sizing for Chiller:Electric:EIR CHILLER - AIR COOLED 1 * ~~~ * User-Specified Reference Condenser Fluid Flow Rate [m3/s] = 15.23400 * ~~~ * differs from Design Size Reference Condenser Fluid Flow Rate [m3/s] = 33.19680 * ~~~ * This may, or may not, indicate mismatched component sizes. The question is, what am I doing wrong here and how can I fix these warnings? And where did it get the idea that the Chillers' Design Size Reference Condenser Fluid Flow Rate should be 33.19680 [m3/s]? Or that on the water cooling coil the Design Size Design Water Flow Rate should be 1.02900E-002 [m3/s]? Thank you! |
2018-01-05 03:48:59 -0500 | edited question | Equipment sizing errors Equipment sizing errors I have an HVAC system consisting of 2 parallel air-cooled chillers, each with a designated pump. |
2018-01-04 16:49:43 -0500 | asked a question | Equipment sizing errors Equipment sizing errors I have an HVAC system consisting of 2 parallel chillers, each with a designated pump. For each o |
2017-12-13 04:35:48 -0500 | received badge | ● Teacher (source) |
2017-12-13 01:06:23 -0500 | answered a question | 100% unmet hours in chilled water system The problem was solved, first by changing the type of chilled beams from passive to active. In addition I put setpoint m |
2017-12-12 10:22:33 -0500 | commented question | 100% unmet hours in chilled water system Thank you. Link: https://drive.google.com/drive/folders/18ytz61lMFpIh9-QkoaN4lpX7L5fPFejC?usp=sharing From what I saw t |
2017-12-12 06:10:37 -0500 | commented question | 100% unmet hours in chilled water system @Avi How can I post a link of my model? I have two chillers that are big enough,however not all their capacity is used ( |
2017-12-11 13:09:26 -0500 | asked a question | 100% unmet hours in chilled water system 100% unmet hours in chilled water system Hi, I have an HVAC system consisting of 2 electric chillers in a college. For s |
2017-11-27 09:46:12 -0500 | received badge | ● Supporter (source) |
2017-11-27 09:46:11 -0500 | marked best answer | Export Variable to CSV measure - year error Hi, I've used the measure "Export Variable to CSV" in order to convert 3 variables to CSV files. I ran my simulation for one day only, 16 May 2016. However, the 3 CSV files show me the results for 16 May 2009. How can this be solved? Thanks! |
2017-11-27 09:46:05 -0500 | commented answer | Export Variable to CSV measure - year error Thank you very much! |
2017-11-27 05:19:47 -0500 | commented question | Export Variable to CSV measure - year error On the weather tab the year is 2016, the epw weather file is taken from Energyplus website ( for Tel-Aviv) and is for ye |
2017-11-26 03:03:49 -0500 | asked a question | Export Variable to CSV measure - year error Export Variable to CSV measure - year error Hi, I've used the measure "Export Variable to CSV" in order to convert 3 var |
2017-11-26 02:23:19 -0500 | commented answer | Exporting full (component-level) simulation results to CSV from OpenStudio Hi, I added 3 output variables through the measures as explained above, and I can see the results in the ResultsViewer a |
2017-11-25 14:05:00 -0500 | asked a question | Modeling a control valve on chilled water loop Modeling a control valve on chilled water loop Hi, I have a system containing two chillers piped in parallel, each with |
2017-11-08 11:06:17 -0500 | commented answer | Openstudio Space Types vs. Spaces So, to sum up the problem: I've deleted default schedules from Space Types->General and as a result, in Space Types |
2017-11-08 08:32:08 -0500 | commented answer | Openstudio Space Types vs. Spaces All the schedules sets are defined for: hours of operation, no. of people, activity, lighting and equipment. They're not |
2017-11-07 04:02:10 -0500 | commented answer | Openstudio Space Types vs. Spaces Is there a way to overcome this? or the only way is to define each space as a different type? Thank you! |
2017-11-04 11:56:05 -0500 | commented answer | Openstudio Space Types vs. Spaces I tried this, however the simulation failed: When I deleted these schedules from Space types it also disappeared from Sp |
2017-11-01 03:41:19 -0500 | commented answer | Openstudio Space Types vs. Spaces Thank you. I did prepare a schedule set for each of the rooms and dropped them in the Space->Properties->General t |
2017-10-31 16:15:38 -0500 | commented answer | Openstudio Space Types vs. Spaces In this case, how can I edit these loads schedules in Space->Loads to be individual for each space? Because the sched |
2017-10-31 15:17:11 -0500 | commented answer | Openstudio Space Types vs. Spaces By "that cell" you mean the schedule sets which are defined in Space->Properties->General or what is shown in gree |
2017-10-31 07:42:05 -0500 | commented answer | Openstudio Space Types vs. Spaces Thanks, Regarding: "Spaces inherit objects from space types, and these will show up in green... You can override these b |
2017-10-30 07:18:28 -0500 | received badge | ● Commentator |
2017-10-30 07:18:28 -0500 | commented question | Openstudio Space Types vs. Spaces Should I just create a different space type for each room? or is there another way to not use the default schedule defin |
2017-10-28 15:49:08 -0500 | asked a question | Openstudio Space Types vs. Spaces Openstudio Space Types vs. Spaces Hi, I would like to model a school with several types of spaces (classrooms, computer |
2017-10-26 13:03:17 -0500 | marked best answer | unassigning spaces in openstudio 2.1.0 I would like to unassign several spaces in my model. How can I do this? On the 0.8 version tutorial it is pretty clear (see attached image). |
2017-10-26 13:02:56 -0500 | marked best answer | running simulation for one day only Can the simulation be run for only one day? And if it so, does the weather file need to contain only one day, or OpenStudio knows how to pick this day from the EPW file? And if I'm running for one day only, can I insert the Design Days information manually for this day only? Thanks very much. |
2017-10-26 13:02:31 -0500 | marked best answer | How to convert CSV/Excel weather file to ddy? Hi, I have an Excel format of weather file for a certain day and I would like to convert it to DDY and upload it in OpenStudio. How can this be achieved? Thanks in advance, Yael |
2017-10-26 13:02:28 -0500 | edited question | How to convert CSV/Excel weather file to ddy? How to cinvert CSV/Excel weather file to ddy? Hi, I have an Excel format of weather file for a certain day and I would l |
2017-10-26 13:01:45 -0500 | marked best answer | Failing to load an Openstudio file I'm having troubles to upload an OSM file to Sketchup: I've just created a simple model in Sketchup, but after saving (using Save Openstudio model) and trying to open it (using Open Openstudio model) I received the following messages: This is not the first time it happens. What can be done to solve this? I'm using: Sketchup Make version 17.2.2555 and Openstudio 2.1.0 |
2017-10-26 13:01:15 -0500 | marked best answer | How to create different floors in sketchup? The Openstudio tutorials I've watched usually draw a space outline and then use the Spaces From Diagram tool to project the diagram into a multistory building. However, I want to create different floors. What is the best approach for this? Also, I tried to use the "Hide" function but it doesn't seem to be working. What could be the reason? |
2017-10-26 13:00:28 -0500 | marked best answer | Editing schedule type in Openstudio In Openstudio: After defining the schedule type to specific type, can I change it? (e.g. from on/off to fraction etc.) Thanks |
2017-10-26 12:43:36 -0500 | marked best answer | defining equipment loads I would like to model a computer room in which every occupant uses 1 computer. I have a schedule for the occupancy and I wish to correlate the equipment load to it. Should I use a multiplier and how? |