First time here? Check out the Help page!
| 2026-04-14 22:01:52 -0500 | commented answer | Location of Preheat coil Thanks for your opinion. This is a requirement for the baseline case. We are happy when the baseline case consumes more |
| 2026-04-14 19:47:17 -0500 | commented answer | Location of Preheat coil I would just like to know the correct interpretation of ASHRAE 90.1 Appendix G. Preheat coil is required in the baseline |
| 2026-04-14 09:50:48 -0500 | commented answer | Location of Preheat coil Say, OA is 0ºC (32ºF), and the indoor heating setpoint is 20ºC (68ºF). The preheat coil heats the air up to 9ºC (48ºF). |
| 2026-03-30 10:18:08 -0500 | commented question | VAV Damper Heating Action Sorry if the link is wrong. I meant to ask about Airterminal:SingleDuct:VAV:Reheat. |
| 2026-03-27 20:12:11 -0500 | received badge | ● Popular Question (source) |
| 2026-03-27 20:07:16 -0500 | marked best answer | VRF Crankcase Heater Operation A bug report EnergyPlus I/O Reference states as follows: Crankcase Heater Power per Compressor: Crankcase heater electrical consumption is applied only when the compressor is off or is applied during the off cycle when the compressor is cycling below the Minimum Heat Pump Part-Load Ratio. Maximum Outdoor Dry-bulb Temperature for Crankcase Heater: This numeric field defines the maximum outdoor temperature, in degrees Celsius, below which the crankcase heater will operate. However, what I observed is the opposite. Crankcase heater electrical consmption is applied when both of the following conditions are met;
It would be nice to see more crankcase heater operation options in the future, but for now, I think the I/O Reference is more relevant. Crankcase heater electric consumption should be applied when the compressor is OFF. The bug can be easily reproduced with ExampleFiles e.g., VariableRefrigerantFlow_5Zone.idf (V25-2-0). |
| 2026-03-27 20:05:22 -0500 | commented answer | VRF Crankcase Heater Operation Thank you! I'll check the operation again with V26-1-0. |
| 2026-03-27 02:40:19 -0500 | commented answer | VAV Damper Heating Action The only case that didn't work well was setting the air terminal min air flow fraction to 0 (although that's unlikely in |
| 2026-03-27 02:28:52 -0500 | commented answer | VAV Damper Heating Action Thank you for the answer. I explored a bit. For heating sizing runs, the air terminal air flow rate did not increase wit |
| 2026-03-27 00:10:52 -0500 | commented question | VRF Crankcase Heater Operation A similar report is found on Github, but it has not been addressed enough. https://github.com/NatLabRockies/EnergyPlus/ |
| 2026-03-26 22:04:31 -0500 | asked a question | VRF Crankcase Heater Operation VRF Crankcase Heater Operation A bug report EnergyPlus I/O Reference states as follows: Crankcase Heater Power per Com |
| 2026-03-26 20:10:31 -0500 | marked best answer | How to get VRF Performance Curve Output Value I would like to get the output values of VRF performnance curves for validation purpose. I tested with an ExampleFile VariableRefrigerantFlow_5Zone.idf (V25-2-0). The output values of the following curves are -999 throughout the year, which indicates the curves are inactive or unused.
FYI, the For 1, it will not be used when CR is less than 1. I reduced the heat pump's For 2, I changed the performance curve coefficients, and the cooling energy use changed. So, the curve is actualy used. I tested all types of How can I get the output of the two curves? |
| 2026-03-26 20:10:21 -0500 | commented answer | How to get VRF Performance Curve Output Value Thanks Greg for taking the time. |
| 2026-03-26 20:06:21 -0500 | commented answer | How to get VRF Performance Curve Output Value I found the results of the curves in the eio file. Thank you so much! |
| 2026-03-25 23:16:38 -0500 | asked a question | How to get VRF Performance Curve Output Value How to get VRF Performance Curve Output Value I would like to get the output values of VRF performnance curves for valid |
| 2026-03-24 20:30:33 -0500 | asked a question | VAV Damper Heating Action VAV Damper Heating Action EnergyPlus I/O Reference, AirTerminal:SingleDuct:ConstantVolume:Reheat, Damper Heating Action |
| 2026-03-18 00:53:52 -0500 | commented question | How to model Night Purge Reported. https://github.com/NatLabRockies/EnergyPlus/issues/11475 |
| 2026-03-17 09:57:50 -0500 | commented answer | Very low COP values for VRF cooling and heating Page 29 mentions the flat part where PLR exceeds 1 in Figure 8 on page 26. The vertical axis of Figure 8 is power input, |
| 2026-03-14 07:02:13 -0500 | received badge | ● Rapid Responder (source) |
| 2026-03-14 07:02:13 -0500 | answered a question | Very low COP values for VRF cooling and heating all other capacity and EIR curves were set to coef 1 = 1, Coefs 2-6 = 0. That's inappropriate. For EIRFPLR, if you |
| 2026-03-11 05:03:06 -0500 | marked best answer | How to model PAU connected to multiple AHUs I want to model HVAC system: PAU (primary air handling unit) + AHU as shown below. One PAU is connected to multiple AHUs. The PAU supplies outdoor air to AHUs.
Can it be modelled in EnergyPlus in the first place? If yes, how can it be modelled? If no, is there any other software that can model it? I tried some tricky modelling as follows, but in vein.
For Failed model 1, I tried to connect For Failed model 2, I added zone 21 and zone 22 and used OutdoorAir:Mixer is essensital for AirLoopHVAC and cannot be deleted. I don't know how to connect PAU supply air duct to AHU1 and AHU2. Currently, I have to compromise and change the Air-side Schematic as shown below.
For Compromise model 1, one large PAU is divided into two small PAUs. For Compromise model 2, There is only one PAU, but it supplies outdoor air to each zone directly. In terms of energy consumption, these HVAC systems might consume almost the same energy as the original system (PAU connected to AHUs), but I want to model the original system and compare with Compromise model 1 and Compromise model 2 in order to confirm it. |
| 2026-03-06 02:13:45 -0500 | received badge | ● Popular Question (source) |
| 2026-03-04 20:16:52 -0500 | marked best answer | EnergyPlus Crashes with Optimum Start for VRF A bug report. I tried modelling optimum start control to zone VRF. I used an ExampleFile: VariableRefrigerantFlow_5Zone.idf (V25-2-0). Originally, The idf file is here. Some findings:
This post is about optimum start for VRF. I wonder if @apdavis or @Julien Marrec has successfully modelled optimum start for zone VRF. |
| 2026-03-04 01:29:41 -0500 | commented answer | EnergyPlus Crashes with Optimum Start for VRF Thank you for your prompt review. The ExampleFile I had tested optimum srart for FCU is 5ZoneFanCoilDOASCool.idf. It h |
| 2026-03-03 02:55:29 -0500 | asked a question | EnergyPlus Crashes with Optimum Start for VRF EnergyPlus Crashes with Optimum Start for VRF A bug report. I tried modelling optimum start control to zone VRF. I use |
| 2026-02-24 21:29:01 -0500 | commented question | How to model Night Purge 5ZoneNightVent2.idf models night purge with ZoneVentilation:DesignFlowRate. That's another option. I'm wondering if Avai |
| 2026-02-24 07:33:03 -0500 | commented question | How to model Night Purge 5ZoneNightVent2.idf models night purge with ZoneVentilation:DesignFlowRate. That's another option. I'm wondering if Avai |
| 2026-02-24 03:28:16 -0500 | asked a question | How to model Night Purge How to model Night Purge Has anyone modelled night purge (night ventilation) in EnergyPlus using AvailabilityManager:Nig |
| 2026-02-12 21:47:58 -0500 | asked a question | Location of Preheat coil Location of Preheat coil I'd like to confirm the location of a preheat coil which is required for ASHRAE PRM Baseline Sy |
| 2025-12-01 18:53:59 -0500 | received badge | ● Self-Learner (source) |
| 2025-12-01 09:10:13 -0500 | answered a question | Severe Error: Found Material that is too thin and/or too highly conductive @Aung I followed the severe error message and changed the thickness of alminum panel from 0.002m to 0.4m. The R-value of |
| 2025-11-25 15:43:52 -0500 | received badge | ● Notable Question (source) |
| 2025-11-22 02:19:19 -0500 | edited question | How can DCV and VAV be compatible in both heating and cooling? How can DCV and VAV be compatible in both heating and cooling? Has anyone been able to successfully implement CO2 based |
| 2025-11-22 02:14:29 -0500 | commented answer | How can DCV and VAV be compatible in both heating and cooling? Supplement: Minimum Outdoor Air Flow Rate in Controller:OutdoorAir does not actually ensure the minimum outdoor air flow |
| 2025-11-13 01:59:30 -0500 | asked a question | Optimum Start Control for Appendix G Baseline Optimum Start Control for Appendix G Baseline Does anyone know if Optimum Start Control needs to be modelled in the Base |
| 2025-11-11 13:34:26 -0500 | commented answer | Central Cooling Design Supply Air Temperature in Sizing:System To be precise, yes, it’s not the case for blow-through. Also, “the temperature at the setpoint node in whatever SetPoint |
| 2025-11-07 05:28:30 -0500 | received badge | ● Popular Question (source) |
| 2025-11-05 02:13:47 -0500 | asked a question | Central Cooling Design Supply Air Temperature in Sizing:System Central Cooling Design Supply Air Temperature in Sizing:System Central Cooling Design Supply Air Temperature in Sizing:S |
| 2025-10-24 03:32:27 -0500 | received badge | ● Popular Question (source) |
| 2025-10-20 02:53:21 -0500 | received badge | ● Self-Learner (source) |
| 2025-09-30 04:28:17 -0500 | marked best answer | Number of Cooling Towers for ASHRAE90.1 Baseline As per the title. Sorry for asking about a very fundamental requirement of ASHRAE90.1 Appendix G, but I'm not 100% sure. What is the number of cooling towers for the Baseline case? I have been modeling Tower per Chiller as shown on the left side of the schematic below. If the Baseline case has 10 chillers, it also has 10 cooling towers. Supporting document: [ANSI/ASHRAE/IES Standard 90.1 Performance Rating Method Reference Manual] (https://www.pnnl.gov/main/publication...)
On the other hand, the original requirement of G3.1.3.11 states that the heat-rejection device shall be an axial-fan open-circuit cooling tower. It also states that each chiller shall be modeled with separate condenser-water pumps. If I interpret these requiremrnts as they are, the schematic would look like the one on the right below.
Which is correct, Tower per Chiller or only one big Tower? The propbem of the only one big Tower is that the condenser loop shown on the right does not work in EnergyPlus. It seems that EnergyPlus does not allow to model condenser pumps immediately before or after chillers. When I modelled the schematic on the right in EnergyPlus, no warning/severe error about component connection appeared, but there was no water flow on the condenser loop. Condenser pumps and one cooling tower did not work. SUPPLEMENT EngineeringReference describes pump placement relus in EnergyPlus.
|
| 2025-09-30 01:33:11 -0500 | commented answer | How to Model AHU with DOAS in DesignBuilder? When will v2025 be officially released? Unfortunately, our company does not allow installation of any beta software. |
| 2025-09-24 03:20:42 -0500 | commented question | ZoneHVAC:ExhaustControl does not work Reported. https://github.com/NREL/EnergyPlus/issues/11228 |
| 2025-09-23 03:17:25 -0500 | asked a question | ZoneHVAC:ExhaustControl does not work ZoneHVAC:ExhaustControl does not work A bug report. I ran an ExampleFile 5ZoneAirCooledWithDOASAirLoop_ExhaustSystem.id |
| 2025-09-16 21:52:13 -0500 | received badge | ● Necromancer (source) |
| 2025-09-16 20:39:32 -0500 | edited answer | fan coil unit control with setpoint deadband I think what @Yingying Tai wants to model is as follows. I also want to model the thermostat control because it is sp |
| 2025-09-16 14:31:59 -0500 | received badge | ● Popular Question (source) |