2023-12-22 08:18:52 -0500 answered a question Horizontal ground heat exchanger

Thanks for your help @Denis Bourgeois. As outlined in your previous instructions, we ran a measure in OpenStudio whic

2023-12-22 07:31:50 -0500 marked best answer Horizontal ground heat exchanger

Edited to provide answers for Denis:

OpenStudio Application version? 1.6.0+53c249a897 (SDK 3.6.1)

does the saved .osm file hold an instance of OS:Site:GroundTemperature:Undisturbed:KusudaAchenbach? No

if so, can you post the .osm excerpt? NA

might as well post the OS:GroundHeatExchanger:HorizontalTrench .osm definition: See below

image description

Thanks!


I created an OpenStudio model with a horizontal ground heat exchanger, but OpenStudio isn’t allowing input of “Undisturbed Ground Temperature Model” in the object “OS:GroundHeatExchanger:HorizontalTrench”. The field is greyed-out and can’t be selected.

The model simulates properly (no crashing) when using default entries for a vertical ground field, but when I switch it for a horizontal ground field and simulate the model it crashes with the following message:

“[BOOST_ASSERT] <2> Assertion modelObject failed on line 175 of class openstudio::model::ModelObject __cdecl openstudio::model::detail::GroundHeatExchangerHorizontalTrench_Impl::undisturbedGroundTemperatureModel(void) const in file D:\OSN\src\model\GroundHeatExchangerHorizontalTrench.cpp.”

Based on this background, can somebody explain what might be wrong with my model to prevent it from simulating a horizontal GSHP field? Is there an input in OpenStudio that will allow me to select an “Undisturbed Ground Temperature Model”? Is the field supposed to be greyed-out?

Can OpenStudio simulate horizontal ground heat exchangers?

(There's a similar question from about 7 years ago--suggesting that there was a problem, but followed by discussion of the problem having been fixed. Perhaps the problem has been reintroduced?)

2023-12-13 08:52:02 -0500 edited question Horizontal ground heat exchanger

Horizontal ground heat exchanger Edited to provide answers for Denis: OpenStudio Application version? 1.6.0+53c249a897

2023-12-11 12:55:13 -0500 received badge  Editor (source)
2023-12-11 12:55:13 -0500 edited question Horizontal ground heat exchanger

Horizontal gournd heat exchanger I created an OpenStudio model with a horizontal ground heat exchanger, but OpenStudio i

2023-12-11 12:54:29 -0500 asked a question Horizontal ground heat exchanger

Horizontal gournd heat exchanger I created an OpenStudio model with a horizontal ground heat exchanger, but OpenStudio i

2023-12-07 13:47:41 -0500 asked a question PAT Measurer Editor not working

PAT Measurer Editor not working I am using PAT 3.6.1. When I try to edit a measure, a black rectangle opens and then cl

2019-11-26 09:29:04 -0500 commented answer Getting "completed datapoint failure" when running PAT

The full computer path that indicates where your project resides on your computer. If the file is on your C drive, for

2019-09-26 08:58:56 -0500 answered a question Are you an Expert in OS/E+ in Ontario, Canada? I'll pay for your assistance!

If you are in or around the Toronto/Mississauga area, I may have some leads for you.

2019-03-25 09:54:09 -0500 commented answer Humidifier:Steam:Gas workaround

Thanks for the suggestion!

2019-03-20 14:35:05 -0500 answered a question Humidifier:Steam:Gas workaround

Since no one else answered this--I am fairly confident the answer is "no"--I wound up modelling an electric humidifier a

2019-03-12 11:26:40 -0500 marked best answer Getting "completed datapoint failure" when running PAT

I have not been able to get PAT to run. I've tried two different computers, I've upgraded to the latest download, I've uninstalled, reinstalled, restarted the computer, etc. I have tried both my own model and measures and an example model and measures. In all cases, I get a "completed datapoint failure" message. I'm new to PAT, so it's possible I'm doing something stupid, but I'm not sure how to go about trouble-shooting this problem. Oh--the model and measures run without errors in OpenStudio.

2019-03-12 11:26:30 -0500 received badge  Self-Learner (source)
2019-01-29 14:34:25 -0500 commented answer What is the quickest way to copy a PAT file?

This is very helpful. Thanks!

2019-01-29 14:33:59 -0500 marked best answer What is the quickest way to copy a PAT file?

I am running multiple PAT runs. The set of design alternatives for each file is very similar, but the base OpenStudio file changes. I don't want to put all runs into a single PAT run. I've been using "save as" to create a new PAT file, and then I tweak the new file appropriately. "Save as" takes a long time--and I'm guessing I am duplicating more than I need to. Is there a quicker way to do this?

2019-01-28 12:45:58 -0500 marked best answer internal server error after successful runs

I have an OpenStudio Parametric Analysis Tool run that appears to run each measure combination successfully. However, when I hit "View Analysis" so I can download the results.csv file, I get the following error: "Executor error during find command: OperationFailed: Sort operation used more than the maximum 33554432 bytes of RAM. Add an index, or specify a smaller limit. (96)" Any clues?

Alternatively--is there a better way to match the very long string of characters identifying a run in the local results folder with the design alternative I've assigned? I've been pulling the long string of characters/design alternative pairing off the results.csv file.

Thanks!

2019-01-28 12:40:00 -0500 asked a question What is the quickest way to copy a PAT file?

What is the quickest way to copy a PAT file? I am running multiple PAT runs. The set of design alternatives for each fi

2019-01-28 12:24:46 -0500 commented answer internal server error after successful runs

Thanks David! I was running locally, and this morning, running on AWS, I didn't get that error. However, I also shorten

2019-01-27 19:21:25 -0500 asked a question internal server error after successful runs

internal server error after successful runs I have an OpenStudio Parametric Analysis Tool run that appears to run each m

2019-01-09 11:30:00 -0500 marked best answer AWS free tier with PAT?

Amazon offers a free trial of AWS. Has anyone tried running the Parametric Analysis Tool with the free tier of EC2?

2019-01-09 11:30:00 -0500 received badge  Scholar (source)
2019-01-07 09:05:34 -0500 asked a question AWS free tier with PAT?

AWS free tier with PAT? Amazon offers a free trial of AWS. Has anyone tried running the Parametric Analysis Tool with t

2018-12-06 13:03:07 -0500 received badge  Teacher (source)
2018-12-06 11:44:40 -0500 answered a question Getting "completed datapoint failure" when running PAT

To reiterate my own solution (also in comments) neither project name nor project path can contain spaces. I saw a video

2018-12-06 10:09:52 -0500 asked a question Humidifier:Steam:Gas workaround

Humidifier:Steam:Gas workaround OpenStudio has an electric humidifier but not a gas humidifier, best I can figure out.

2018-10-22 16:51:07 -0500 received badge  Supporter (source)
2018-10-22 11:37:08 -0500 commented question Getting "completed datapoint failure" when running PAT

Apparently I can't yet answer my own questions, but I'll leave this here just in case it helps someone. Best I can tell

2018-10-21 13:13:40 -0500 commented question Getting "completed datapoint failure" when running PAT

No issues with any of these files when running just in OpenStudio.

2018-10-21 08:23:48 -0500 commented question Getting "completed datapoint failure" when running PAT

I am unable to find a version number for PAT--it's the version that downloaded with OpenStudio 2.7.0. I also tried the

2018-10-21 07:45:30 -0500 received badge  Student (source)
2018-10-20 21:40:54 -0500 asked a question Getting "completed datapoint failure" when running PAT

Getting "completed datapoint failure" when running PAT I have not been able to get PAT to run. I've tried two different