An old workaround for this is to use Boiler:HotWater with the efficiency set to a desired average COP of say 1.2. You'll have to edit the IDD to remove the "\maximum 1.0" line in this input field.
N2 , \field Nominal Thermal Efficiency
\required-field
\type real
\minimum> 0.0
\maximum 1.0