An old workaround for this is to use Boiler:HotWater with the efficiency set to a desired average COP of say 1.2. You'll have to edit the IDD to remove the "\maximum 1.0" line in this input field.

N2 , \field Nominal Thermal Efficiency
     \required-field
     \type real
     \minimum> 0.0
     \maximum 1.0