Both of these approaches should work, and they did for this coil type until EnergyPlus v9.5. AirloopHVAC:UnitarySystem with setpoint control and water-to-air heat pump coils will be fixed in v23.1 along with some other related issues.

Other coil types are working correctly in AirloopHVAC:UnitarySystem with Setpoint control, but there is some inconsistency about the need for specifying the setpoint control node in coils such as Coil:Heating:Electric. This will also be cleaned up in v23.1 (March 2023 release).

https://github.com/NREL/EnergyPlus/pull/9814

https://github.com/NREL/EnergyPlus/issues/9793