First time here? Check out the Help page!
1 | initial version |
The cycling PTAC units in OpenStudio's HVAC library are configured with FanOnOff and will cycle the fan on and off with the DX coil. The non cycling PTAC units are configured with FanConstantVolume and will run the fan according the PTAC availability schedule even if the coils are inactive.
2 | No.2 Revision |
The cycling PTAC units in OpenStudio's HVAC library are configured with FanOnOff and will cycle the fan on and off with the DX coil. coils. The non cycling PTAC units are configured with FanConstantVolume and will run the fan according the PTAC availability schedule even if the coils are inactive.