First time here? Check out the Help page!
1 | initial version |
After a little more investigation, I found that the bug occurs when the following two conditions are met:
ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
in the AirLoop and ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
in some zones are connected to the same AirConditioner:VariableRefrigerantFlow
AirLoopHVAC
which does not have ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
.I have narrowed down the cause of the bug ro some extent, which is OK for me for now.
2 | No.2 Revision |
After a little more investigation, I found that the bug occurs when the following two conditions are met:
ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
in the AirLoop and ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
in some zones are connected to the same AirConditioner:VariableRefrigerantFlow
AirLoopHVAC
which does not have ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
.I have narrowed down the cause of the bug ro to some extent, which is OK for me for now.