The baseline and proposed models must use the same method per Table G3.1 No. 6. Lighting.
Baseline Building Performance
Lighting power in the baseline building design shall be determined using the same categorization procedure (building area or space-by-space method) and categories as the proposed design with lighting power set equal to the maximum allowed for the corresponding method and category in Section 9.2...
You can use more than one Building Area Method building type for buildings that have distinct areas, such as parking garages.