You might try using the min/max schedules in the outdoor air controller to replicate your schedule. Use a fractional schedule (OA flow / Max OA flow) to determine the flow rate needed then use this schedules name for both the min and max schedule name inputs.

Controller:OutdoorAir,
  A12, \field Minimum Fraction of Outdoor Air Schedule Name
       \type object-list
       \object-list ScheduleNames
       \note schedule values multiply the design/mixed air flow rate
  A13, \field Maximum Fraction of Outdoor Air Schedule Name
       \type object-list
       \object-list ScheduleNames
       \note schedule values multiply the design/mixed air flow rate