First time here? Check out the Help page!
1 | initial version |
In the ZoneHVAC:IdealLoadsAirSystem object
, if you want the district cooling/heating values to match what is delivered to the zone, then you need to have zero outdoor air, and no dehumidification or humidification:
ZoneHVAC:IdealLoadsAirSystem,
. . .
None, !- Dehumidification Control Type
, !- Cooling Sensible Heat Ratio {dimensionless}
None, !- Humidification Control Type
, !- Design Specification Outdoor Air Object Name