The warnings about invalid ScheduleTypeLimits can be eliminated by replacing the quoted ScheduleTypeLimits.

The warnings about operating DX Cooling Coils at too low temperatures are physically reasonable, therefore the best way to avoid such warnings is to switch off operation whenever these conditions occur, which can be done by EMS instructions.

I have had problems operating air-water heat pumps at temperatures below EnergyPlus standard limits. In these case, it was possible to overcome the problem by modifying the Energy+.idd file.