First time here? Check out the Help page!
1 | initial version |
Not sure whether this is all water under the bridge but I've found the reported cop to be COP ref * EIRfT * EIRfPLR / PLR. I would have thought it would just be COP ref * EIRfT * EIRfPLR. Wish the manual had better definitions of the output variables.
2 | No.2 Revision |
Not sure whether this is all water under the bridge but I've found the reported cop to be COP ref 1 / ( 1/COPref * EIRfT * EIRfPLR / PLR. PLR). I would have thought it would just be COP ref 1 / (1/COPref * EIRfT * EIRfPLR. EIRfPLR). Wish the manual had better definitions of the output variables.
3 | No.3 Revision |
Not sure whether this is all water under the bridge but I've found the reported cop to be 1 / ( 1/COPref * EIRfT * EIRfPLR / PLR). I would have thought it would just be 1 / (1/COPref * EIRfT * EIRfPLR). Wish the manual had better definitions of the output variables.variables. Eventually found this answer on the E+ website which straightened me out.
http://energyplus.helpserve.com/Knowledgebase/Article/View/61/25/eir-chiller-power-calculation