First time here? Check out the Help page!
1 | initial version |
Yes, EnergyPlus Airflow Network (Natural Ventilation) does not affect the thermal properties of operated windows. An approach would be using EMS Surface Construction State actuator to change the window properties (to a clear glass), which involves certain experience with EMS to sync those changes with the opening of the windows.