If you are autosizing, set the averaging window to 1 hour or more (3 time steps). If not autosizing, then the system may be oversized.

Sizing:Parameters, 1, !- Heating Sizing Factor 1, !- Cooling Sizing Factor 3; !- Timesteps in Averaging Window

If you are autosizing, set the averaging window to 1 hour or more (3 time steps). If not autosizing, then the system may be oversized.

Sizing:Parameters,
  1,                                      !- Heating Sizing Factor
  1,                                      !- Cooling Sizing Factor
  3;                                      !- Timesteps in Averaging Window