The report variables for Zone People Occupant Count is associated with the People object, not the zone. Change the key value to West Zone People
.
Regarding the Standard Ratings warnings, the performance curve values do not allow the model to extrapolate the data outside the min/max value of x (indoor WB) and y (outdoor DB) range specified. You can safely (usually) adjust those values to include the rating point. See Engineering Reference document, section Standard Rating of Single-Speed DX Cooling Coils
for the rating points.
Curve:Biquadratic,
SPACE1-1 PTAC Cooling Coil Cap-FT, !- Name
0.942587793, !- Coefficient1 Constant
0.009543347, !- Coefficient2 x
0.00068377, !- Coefficient3 x**2
-0.011042676, !- Coefficient4 y
0.000005249, !- Coefficient5 y**2
-0.00000972, !- Coefficient6 x*y
12.77778, !- Minimum Value of x
23.88889, !- Maximum Value of x
18.0, !- Minimum Value of y
46.11111; !- Maximum Value of y