The report variables for Zone People Occupant Count is associated with the People object, not the zone. Change the key value to West Zone People.

Regarding the Standard Ratings warnings, the performance curve values do not allow the model to extrapolate the data outside the min/max value of x (indoor WB) and y (outdoor DB) range specified. You can safely (usually) adjust those values to include the rating point. See Engineering Reference document, section Standard Rating of Single-Speed DX Cooling Coils for the rating points.

Curve:Biquadratic,
  SPACE1-1 PTAC Cooling Coil Cap-FT,                       !- Name
  0.942587793,                                             !- Coefficient1 Constant
  0.009543347,                                             !- Coefficient2 x
  0.00068377,                                              !- Coefficient3 x**2
  -0.011042676,                                            !- Coefficient4 y
  0.000005249,                                             !- Coefficient5 y**2
  -0.00000972,                                             !- Coefficient6 x*y
  12.77778,                                                !- Minimum Value of x
  23.88889,                                                !- Maximum Value of x
  18.0,                                                    !- Minimum Value of y
  46.11111;                                                !- Maximum Value of y