At times your On-Site production is exporting to the grid because it is higher than the demand it needs to cover.
So in all, you bought from the Utility 1,436,312 kWh, but you also exported 6,236 kWh, so the Net is difference between the two, so 1,430,075 kWh.
If you didn't have On Site production, you would have bought 1,430,075 kWh + 284,130 kWh.
2 | No.2 Revision |
At times your On-Site production is exporting to the grid because it is higher than the demand it needs to cover.
So in all, you bought from the Utility 1,436,312 kWh, but you also exported 6,236 kWh, so the Net is difference between the two, so 1,430,075 kWh.
If you didn't have On Site production, you would have bought 1,430,075 kWh + 284,130 kWh = 1,714,205 kWh.
3 | No.3 Revision |
At times your On-Site production is exporting to the grid because it is higher than the demand it needs to cover.
So in all, you bought from the Utility 1,436,312 kWh, but you also exported 6,236 kWh, so the Net is difference between the two, so 1,430,075 kWh.
If you didn't have On Site production, you would have bought 1,430,075 kWh + 284,130 kWh = 1,714,205 kWh.
Check out the Engineering Reference for [Whole-Facility Electric Service](https://bigladdersoftware.com/epx/docs/8-8/engineering-reference/whole-facility-electric-service.html#section-whole-facility-electric-service
4 | No.4 Revision |
At times your On-Site production is exporting to the grid because it is higher than the demand it needs to cover.
So in all, you bought from the Utility 1,436,312 kWh, but you also exported 6,236 kWh, so the Net is difference between the two, so 1,430,075 kWh.
If you didn't have On Site production, you would have bought 1,430,075 kWh + 284,130 kWh = 1,714,205 kWh.
Check out the Engineering Reference for [Whole-Facility Whole-Facility Electric Service](https://bigladdersoftware.com/epx/docs/8-8/engineering-reference/whole-facility-electric-service.html#section-whole-facility-electric-serviceService